Introduction
Brick work is one of the most basic and important activities in building constructions. From residential houses to commercial and high rise building. Brick work is a very common item in building constructions. I have explained very important interview questions for billing engineers, site engineers and quantity surveyors.
This article clearly explains Brick work in very simple language, suitable for Site Engineer , Billing Engineer, While strictly Following CPWD Specifications brick work.
It is specially useful Billing engineer, site Engineer.
What is Brick work ?
Brickwork is the constructions of wall by laying
bricks in a proper pattern using cement mortar with proper line, level and
bonding as per drawing and follow the
CPWD specifications guideline.Brick + Mortar = Brickwork
Brickwork is the constructions of wall by laying bricks in a proper pattern using cement mortar with proper line, level and bonding as per drawing and follow the CPWD specifications guideline.
Types of Brick Bonds
1. English Bond
Alternate courses of stretchers and Headers Use in 230MM thick wall,
very strong used for load-bearing walls.
2. Flemish Bond
Each course has one stretcher + one header alternately
3. Stretcher Bond
All brick laid lengthwise joint staggered
4. Header bond
All brick laid headers, used for Soak Pit , Rain water Harvesting Pit,
Curved wall.
5. Stack Bond
brick placed directly one above another vertical joints aligned.
6. Garden wall Bond
Usually 3 stretchers + 1 header pattern, used for boundary wall.
7. Herringbone Bond
Brick laid in zig-zag pattern, used in flooring and paving work.
8. Honey Comb brick bond
Forming a pattern that looks like a honeycomb brick work
Basic rules of brick work item specification in
BOQ
Below Ground Brick work in foundation level
measure in cubic meter generally use 230MM thick wall Ratio Is ( 1 :6 )
above Ground Brick work in Super structure measure in cubic meter generally use 230MM thick
wall Ratio Is ( 1 :6 ) Both brick work are measure separately otherwise
specified in BOQ.
Half Brick work single layer 115 thick wall Ratio Is ( 1 :4 ) measure in square meter separately otherwise
specified in BOQ.
Half brick work use in partition , toilet wall providing every 3rd
layer brick 6MM to not exceed 8MM dia 2nos M.S bar.
Over laps in
reinforcement, if any shall not be less than 300MM
Dimensions and Tolerances of bricks
DIMENSIONS AND
TOLERANCES OF BRICK
Is 1077 clause 6.1 Dimensions
Clause 6.1.1 The standard modular size of common
building bricks shall be as follows.
Sr. no.
Types of brick
Length MM
Width MM
Height MM
1
Modular Brick
190 MM
90 MM
90 MM
2
Modular Brick (Tile)
190 MM
90 MM
40 MM
Clause 6.1.2 The standard Non-modular size of
common building bricks shall be as follows.
Sr. no.
Types of brick
Length MM
Width MM
Height MM
1
Non-Modular Brick
230 MM
110 MM
70 MM
2
Non-Modular Brick (Tile)
230 MM
110 MM
30 MM
CPWD Clause 6.1.5.2 Individual tolerance of bricks shall be as
follows.
1
Modular Brick
190 + - 7MM
90 + - 4 MM
90 + - 4 MM
2
Non-Modular Brick
230 + - 10MM
110 + - 7MM
70 + - 4 MM
Classifications of brick
Cpwd specifications clause 6.1.2 Table 6.2
Brick are classified based on compressive strength, that is how much load they
can carry, low strength for light work, Medium for normal buildings, and high
strength for heavy structures.
Minimum compressive strength as given below .
CLASSIFICATION OF
BRICKS
Cpwd specifications clause 6.1.1
Table 6.2
Average compressive strength of brick
in (N/mm²)
Sr. no.
Class Designation
Not Less Than (N/mm²)
Less Than (N/mm²)
1
12.5
12.5 N/mm²
15 N/mm²
2
10
10 N/mm²
12.5 N/mm²
3
7.5
7.5 N/mm²
10 N/mm²
4
5
5 N/mm²
7.5 N/mm²
5
3.5
3.5 N/mm²
5 N/mm²
1. Consumption
of cement and brick
Description of Item
Number of brick
Cement quantity
Remark &
Description of work
BRICK WORK MASONRY
Modular bricks
Ratio ( 1:4 )
486 Nos Brick in 1
Cum
83.6 kg cement in 1
cum
380 kG cement in 1
Cum Motors for 9 inches brick work 0.22 Cum motors use in one cum brick brick
Modular bricks
Ratio ( 1:6 )
486 Nos Brick in 1
Cum
55 kg cement in 1
cum
250 kG cement in 1
Cum Motors for 9 inches brick work 0.22 Cum motors use in one cum brick brick
Non modular brick
Ratio ( 1:4 )
494 Nos Brick in 1
Cum
95 kg cement in 1
cum
380 kG cement in 1
Cum Motors for 9 inches brick work 0.25 Cum motors use in one cum brick brick
Non modular brick
Ratio ( 1:6 )
494 Nos Brick in 1
Cum
62.5 kg cement in
cum
250 kG cement in 1
Cum Motors for 9 inches brick work 0.25 Cum motors use in one cum brick brick
HALF BRICK MASONRY
Half brick masonry
Ratio ( 1:3 )
56.5 Nos Brick in 1
Sqmr
14.28 kg cement in
1 Sqmr
1428 kG cement in
100 SQMR Motors for 4 inches brick work 14.28KG motors use in 100 SQMR brick
brick
Half brick masonry
Ratio ( 1:4 )
56.5 Nos Brick in 1
Sqmr
10.64 kg cement 1
Smqr
1068 kG cement in
100 SQMR Motors for 4 inches brick work 10.64KG motors use in 1 SQMR brick
brick
Measurement book with Example
Brick work Deduction rules
PROJECT NAME
Sun Tower Greater
Noida
CLIENT NAME
Onsite XL
CONTRACTOR NAME
SANGEETA DEVI
RUNNING BILL No.
RA-01
MEASUREMENT BOOK
S.No.
Description
Unit
No.
No.
L
B
H
Qty.
Remarks
EXAMPLE -1
Plain Wall
Wall
cum
1
1
5
0.23
3
3.45
Final quantity
3.45 cum
EXAMPLE -2
Wall with small
opening upto 0.01 cum
Wall
cum
1
1
4
0.23
3
2.76
Beam in wall
cum
1
1
0.2
0.23
0.15
0.0069
No Deduction
Final quantity
2.76 cum
EXAMPLE -3
Wall with opening
above 0.01 cum
Wall
cum
1
1
6
0.23
3
4.14
Exhaust fan
cum
-1
1
0.3
0.23
0.3
-0.02
Deduction above
0.01 cum area
Wall
cum
1
1
3
0.23
3
2.07
Height 1.5 +.23 M = 1.73M
Window 1.5 M X 1.5M
cum
-1
1
1.5
0.23
1.73
-0.60
Deduction above
0.01 cum including lintel depth
Final quantity
5.59 cum
Total quantity
11.80
Previous
0.00
This Bill
11.80
Alternate courses of stretchers and Headers Use in 230MM thick wall, very strong used for load-bearing walls.
2. Flemish Bond
Each course has one stretcher + one header alternately
3. Stretcher Bond
All brick laid lengthwise joint staggered
4. Header bond
All brick laid headers, used for Soak Pit , Rain water Harvesting Pit, Curved wall.
5. Stack Bond
brick placed directly one above another vertical joints aligned.
6. Garden wall Bond
Usually 3 stretchers + 1 header pattern, used for boundary wall.
7. Herringbone Bond
Brick laid in zig-zag pattern, used in flooring and paving work.
8. Honey Comb brick bond
Forming a pattern that looks like a honeycomb brick work
Basic rules of brick work item specification in
BOQ
Below Ground Brick work in foundation level
measure in cubic meter generally use 230MM thick wall Ratio Is ( 1 :6 )
above Ground Brick work in Super structure measure in cubic meter generally use 230MM thick
wall Ratio Is ( 1 :6 ) Both brick work are measure separately otherwise
specified in BOQ.
Half Brick work single layer 115 thick wall Ratio Is ( 1 :4 ) measure in square meter separately otherwise
specified in BOQ.
Half brick work use in partition , toilet wall providing every 3rd
layer brick 6MM to not exceed 8MM dia 2nos M.S bar.
Over laps in
reinforcement, if any shall not be less than 300MM
above Ground Brick work in Super structure measure in cubic meter generally use 230MM thick wall Ratio Is ( 1 :6 ) Both brick work are measure separately otherwise specified in BOQ.
Half Brick work single layer 115 thick wall Ratio Is ( 1 :4 ) measure in square meter separately otherwise specified in BOQ.
Half brick work use in partition , toilet wall providing every 3rd layer brick 6MM to not exceed 8MM dia 2nos M.S bar.
Over laps in reinforcement, if any shall not be less than 300MM
|
DIMENSIONS AND
TOLERANCES OF BRICK |
||||
|
Is 1077 clause 6.1 Dimensions |
||||
|
Clause 6.1.1 The standard modular size of common
building bricks shall be as follows. |
||||
|
Sr. no. |
Types of brick |
Length MM |
Width MM |
Height MM |
|
1 |
Modular Brick |
190 MM |
90 MM |
90 MM |
|
2 |
Modular Brick (Tile) |
190 MM |
90 MM |
40 MM |
|
Clause 6.1.2 The standard Non-modular size of
common building bricks shall be as follows. |
||||
|
Sr. no. |
Types of brick |
Length MM |
Width MM |
Height MM |
|
1 |
Non-Modular Brick |
230 MM |
110 MM |
70 MM |
|
2 |
Non-Modular Brick (Tile) |
230 MM |
110 MM |
30 MM |
|
CPWD Clause 6.1.5.2 Individual tolerance of bricks shall be as
follows. |
||||
|
1 |
Modular Brick |
190 + - 7MM |
90 + - 4 MM |
90 + - 4 MM |
|
2 |
Non-Modular Brick |
230 + - 10MM |
110 + - 7MM |
70 + - 4 MM |
Classifications of brick
Cpwd specifications clause 6.1.2 Table 6.2
Brick are classified based on compressive strength, that is how much load they
can carry, low strength for light work, Medium for normal buildings, and high
strength for heavy structures.
Minimum compressive strength as given below .
CLASSIFICATION OF
BRICKS
Cpwd specifications clause 6.1.1
Table 6.2
Average compressive strength of brick
in (N/mm²)
Sr. no.
Class Designation
Not Less Than (N/mm²)
Less Than (N/mm²)
1
12.5
12.5 N/mm²
15 N/mm²
2
10
10 N/mm²
12.5 N/mm²
3
7.5
7.5 N/mm²
10 N/mm²
4
5
5 N/mm²
7.5 N/mm²
5
3.5
3.5 N/mm²
5 N/mm²
Brick are classified based on compressive strength, that is how much load they can carry, low strength for light work, Medium for normal buildings, and high strength for heavy structures.
Minimum compressive strength as given below .
|
CLASSIFICATION OF
BRICKS |
|||
|
Cpwd specifications clause 6.1.1
Table 6.2 |
|||
|
Average compressive strength of brick
in (N/mm²) |
|||
|
Sr. no. |
Class Designation |
Not Less Than (N/mm²) |
Less Than (N/mm²) |
|
1 |
12.5 |
12.5 N/mm² |
15 N/mm² |
|
2 |
10 |
10 N/mm² |
12.5 N/mm² |
|
3 |
7.5 |
7.5 N/mm² |
10 N/mm² |
|
4 |
5 |
5 N/mm² |
7.5 N/mm² |
|
5 |
3.5 |
3.5 N/mm² |
5 N/mm² |
1. Consumption
of cement and brick
|
Description of Item
|
Number of brick |
Cement quantity |
Remark &
Description of work |
|
BRICK WORK MASONRY |
|
|
|
|
Modular bricks
Ratio ( 1:4 ) |
486 Nos Brick in 1
Cum |
83.6 kg cement in 1
cum |
380 kG cement in 1
Cum Motors for 9 inches brick work 0.22 Cum motors use in one cum brick brick |
|
Modular bricks
Ratio ( 1:6 ) |
486 Nos Brick in 1
Cum |
55 kg cement in 1
cum |
250 kG cement in 1
Cum Motors for 9 inches brick work 0.22 Cum motors use in one cum brick brick |
|
Non modular brick
Ratio ( 1:4 ) |
494 Nos Brick in 1
Cum |
95 kg cement in 1
cum |
380 kG cement in 1
Cum Motors for 9 inches brick work 0.25 Cum motors use in one cum brick brick |
|
Non modular brick
Ratio ( 1:6 ) |
494 Nos Brick in 1
Cum |
62.5 kg cement in
cum |
250 kG cement in 1
Cum Motors for 9 inches brick work 0.25 Cum motors use in one cum brick brick |
|
HALF BRICK MASONRY |
|
|
|
|
Half brick masonry
Ratio ( 1:3 ) |
56.5 Nos Brick in 1
Sqmr |
14.28 kg cement in
1 Sqmr |
1428 kG cement in
100 SQMR Motors for 4 inches brick work 14.28KG motors use in 100 SQMR brick
brick |
|
Half brick masonry
Ratio ( 1:4 ) |
56.5 Nos Brick in 1
Sqmr |
10.64 kg cement 1
Smqr |
1068 kG cement in
100 SQMR Motors for 4 inches brick work 10.64KG motors use in 1 SQMR brick
brick |
Measurement book with Example
Brick work Deduction rules
PROJECT NAME
Sun Tower Greater
Noida
CLIENT NAME
Onsite XL
CONTRACTOR NAME
SANGEETA DEVI
RUNNING BILL No.
RA-01
MEASUREMENT BOOK
S.No.
Description
Unit
No.
No.
L
B
H
Qty.
Remarks
EXAMPLE -1
Plain Wall
Wall
cum
1
1
5
0.23
3
3.45
Final quantity
3.45 cum
EXAMPLE -2
Wall with small
opening upto 0.01 cum
Wall
cum
1
1
4
0.23
3
2.76
Beam in wall
cum
1
1
0.2
0.23
0.15
0.0069
No Deduction
Final quantity
2.76 cum
EXAMPLE -3
Wall with opening
above 0.01 cum
Wall
cum
1
1
6
0.23
3
4.14
Exhaust fan
cum
-1
1
0.3
0.23
0.3
-0.02
Deduction above
0.01 cum area
Wall
cum
1
1
3
0.23
3
2.07
Height 1.5 +.23 M = 1.73M
Window 1.5 M X 1.5M
cum
-1
1
1.5
0.23
1.73
-0.60
Deduction above
0.01 cum including lintel depth
Final quantity
5.59 cum
Total quantity
11.80
Previous
0.00
This Bill
11.80
PROJECT NAME
Sun Tower Greater
Noida
CLIENT NAME
Onsite XL
CONTRACTOR NAME
SANGEETA DEVI
RUNNING BILL No.
RA-01
MEASUREMENT BOOK
S.No.
Description
Unit
No.
No.
L
B
H
Qty.
Remarks
EXAMPLE -1
Plain Wall
Wall
cum
1
1
5
0.23
3
3.45
Final quantity
3.45 cum
EXAMPLE -2
Wall with small
opening upto 0.01 cum
Wall
cum
1
1
4
0.23
3
2.76
Beam in wall
cum
1
1
0.2
0.23
0.15
0.0069
No Deduction
Final quantity
2.76 cum
EXAMPLE -3
Wall with opening
above 0.01 cum
Wall
cum
1
1
6
0.23
3
4.14
Exhaust fan
cum
-1
1
0.3
0.23
0.3
-0.02
Deduction above
0.01 cum area
Wall
cum
1
1
3
0.23
3
2.07
Height 1.5 +.23 M = 1.73M
Window 1.5 M X 1.5M
cum
-1
1
1.5
0.23
1.73
-0.60
Deduction above
0.01 cum including lintel depth
Final quantity
5.59 cum
Total quantity
11.80